Electrical formulas

Ohm’s law, power, series and parallel resistance, and US conductor colors.

By Tasker · updated Oct 15, 2026

0 ▲

Ohm’s law

Find Formula
Voltage (V) V = I × R
Current (A) I = V ÷ R
Resistance (Ω) R = V ÷ I

Ohm’s law

Current—
Voltage—
Resistance—
Power (from V and I)—

Power

Find Formula
Power (W), DC or resistive AC P = V × I = I² × R = V² ÷ R
Single-phase AC real power (W) P = V × I × PF
Three-phase AC real power (W) P = √3 × V(line-to-line) × I × PF
Apparent power (VA) S = V × I (single-phase), √3 × V × I (three-phase)
Horsepower 1 hp = 746 W

PF is the power factor, between 0 and 1. For purely resistive loads such as heaters, PF = 1.

Series and parallel resistance

Arrangement Total
Series R = R1 + R2 + R3 + …
Parallel 1/R = 1/R1 + 1/R2 + 1/R3 + …
Two in parallel R = (R1 × R2) ÷ (R1 + R2)

US conductor colors

Conductor Color
Equipment grounding Green, green with yellow stripes, or bare
Grounded (neutral) White or gray
Ungrounded (hot), 120/240 V Commonly black and red, plus blue on three-phase
Ungrounded (hot), 277/480 V Commonly brown, orange and yellow

The NEC sets the grounding and neutral colors. Hot conductor colors are a convention and may be set by local code or the job specification.

Sources

  • NFPA 70, National Electrical Code (NEC), Article 200 (grounded conductors) and 250.119 (equipment grounding conductors).
  • Standard circuit theory. Check your local code and the authority having jurisdiction for anything installed.